Mend Pressure Heating Turned

pressure?

Every time i have had the heating on why do i have to put the pressure up everytime i have turned it off

Mandy
November 2009
System pressure should be set cold at approx 1.2 - 1.5 bar on the guage. when heating is on, pressure will rise upto 1.8/2bar. If pressure reaches towards 3bar, water will discharge from the pipe outside to protect boiler. when it cools pressure will be down because water has been lost. If this is the case, expansion vessel is at fault

chris m - ravenheat specialist
November 2009