Sabre 28MTN Boiler Water releasing water problem?. ?
Please can anyone help? We have just moved into our new home and fitted is a SABRE 28MTN Combi Boiler. We have noriced that when the boiler is on a trickle of water runs from the pipe outside and down the wall. Please can anyone advise what the problem maybe?,thank you Rob (There is no fault LED just the normal 6 second green light flash)
Hi Steve Thank you, The Bar reading is around 2.8, I shall bleed a few radiators and drop to around 1.5 and hopefully it will stop,thank you again Rob
Robnotts
June 2012
Sounds like its overpressure...Check pressure in boiler.. When running the water expands and its getting over the 3 bar max and releasing through the prv...
Steve
June 2012