Alternating FL - flame loss.
Reset by pressing small button for three seconds.
If boiler will not reset then the V9 control box is faulty.
If it resets and attempts to start - check for voltage at gas valve and at ignition generator, verify gas supply is ok, verify condense trap is not blocked.
If there is voltage at gas valve it may be faulty, if there is voltage at ign gen it may be faulty. Usually the ignition spark is audible , top right of heat engine.
Verify fan is running. FL is a general fault to do with flame loss and can be caused by any of the above being faulty.