I have an oil Worchester heatslave which is gravity fed central heating ?
and is not pressurised at the moment although I would now like to convert it over and fit a filling loop. It has an expansion vessil and pressure gauge although was installed with an F and E tank in the attic which we now need to remove for a loft conversion.
Great thanks for the advice. I've now worked out why it was installed with the F&E tank. The boiler is in the centre of the house with a conventional flue and there was no where to discharge a pressure relief, which I'll now obviously require. I'll have to rethink my plans.
Thanks for the advice again
Gregg
Gregg
January 2011
Most boilers can be pressurised. Simple as capping off the cold feed and expansion pipes to the F&E tank, and fitting a filling loop in the system, if the boiler already has an expansion vessel, it's already designed to be pressurised, job done
Carefree
January 2011
as far as i know the boilers are the same but i would phone worcester technical helpline to be on the safe side
brian
January 2011
I can answer this question...
I have an oil Worchester heatslave which is gravity fed central heating ?