Is Pump Working? if not Repair/Repalce
Using Digital Thermometer
What is Temperature of Flow & Return At Boiler, if flow temp above 80'C repalce Thermistor
if not and boiler trips at less than 95'C Repalce Overheat Stat,
Diferential temperature between Flow & Return should be around 10-15'C, this would indicate correct flow rate thro boiler
There could be other causes such as pcb, or excessive Burner gas Pressure
So Best to get an Engineer in