Glow-worm combi boiler 100e information urgently needed?
where is the diverter valve on a Glow-worm 100e combi boiler and what do i need to do to change the diaphragm as i have been informed it is a common fault when heating is fine but hot water doesnt run.?
alan fenlon.hopefully very grateful to someone out there.
October 2007
its a brass round flat valve with machine screws holding it together, with 2 thin pipes comming off it.
to fix you will have to shut off the flow and return valves and the cold supply to the boiler, drain the pressure ( with PRV is quick) undo valve assemble and change diaphram. quite easy but id google for a service manual to study before you attempt
col
October 2007
if you need to ask such a basic question are you really up to doing the job yourself????
Paul the gas man
October 2007
I can answer this question...
Glow-worm combi boiler 100e information urgently needed?