Pressure had dropped due to bleeding. Bled again (not used much during the summer) and pressure dropped below 0.7 bar (should be 1.0 bar). Red light came on and boiler cut out. However, turning the filling loop knob has no effect at all. According to the instructions it's as straightforward as turning it gently until pressure rises appropriately - does this mean the valve is broken? How much are new ones likely to cost do you think?
You need to replace the filling loop which is straightforward (system needds to be drained)> They cost approx £35 from a good plumbing spares supplier such as Plumb Center or Plumbing Trade Suipplies.
Neil - CW Plumbing
February 2011