All is well now, the motor rewound and reinstalled and is better than before more quiet and smooth as a new bearing was also fitted which is what caused the initial failure, the applaince was serviced back in May 2010, and it passed Ok then, I have cleaned the air filters, refitted everything back and checked the HE whilst the fan was out and sounded good with no cracks and any rust etc, vaccumed all around the cupboard and the mesh filter and the heating works fine now and another service is due in May again this year.
also bought a Kidde Night Hawk CO Alarm, which was tested to make sure it really works on co presence, so smoking a cigarette registered 47ppm within about 5 minutes, and the unit was reset completely and left in front of the warm air grill/vent/register as it may be called, and after running it for several days it has not even registered anything, not even a few PPM, so quite confident the system is safe. I also carried out some spillage test and draft test and all seemed fine as a smoke match indicated correct smoke suction through the bottom applaince vent so no downward draftb from the flue, (Spillage) and checked the flue by going up my loft and it seems quite sound and no cracks or displacement from the ridge.
Total cost to rewound the motor was under £50.00, so well pleased with the outcome.
Mike
January 2011