Recent: How to recoil the starter spring - Champion R484TR?

Mend Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Mend repair fix home heating systems

Mend > Home Heating Systems

Mend Heating, Home Heating Systems

Boiler pressure too low then too high!?

Hi. Recently the pressure in my boiler constantly drops to practically zero. To turn the heating on I release water into the boiler to bring the pressure back up to 1 bar. After the heating being on for about 15 minutes the pressure shoots up to over 3 bar at which stage I turn off the heating so it doesn't explode. The pressure quickly drops to below 1 bar again. Does anyone know what could be causing this?

Gerty
March 2010
the expansion vessel is kaput

ian
March 2010
your boiler expansion vessel is possibly EMPTY and needs a recharge of AIR via a car foot pump,find the valve on expansion vessel, remove the cap,test pressure then inflate via the car valve to about 1 bar, or approx 15 psi. then re pressurize the waterside backup to 1 to 1.5 bar

wirecutterman
March 2010

Automatic Answer

We may have found other answers which could help you.

Click here for Boiler Pressure Too Low Too High

Mend Heating, Home Heating Systems
Mend repair fix home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Mend repair fix home heating systems