the pressure vessel just inflate to 1 bar pressure with a car pump (DOES NOT NEED BLEEDING ANY MORE) (unless to much pressure applied ) this can be done providing the water pressure gauge indicates 0 (no pressure in boiler to flex diaphragm rubber )
Now repressurise the heating side using your filler loop
up to 1.5 bar pressure cold, (do not drain system as you lose inhibitor) bled the rads ,check boiler pressure again as a top up may be required
when you are happy with all rads being hot and air free
isolate the filler loop