how can I refire my Worcester greenstar 28 HE boiler?
I bleed radiator this caused a pressure drop and tripped the boiler out. I have topped up system but red light flashing and fault EA showing can't find instructions
I have a Greenstar Worcester 42I, I got an with the EA error code this morning with overnight temperatures reported as low as -7C. It turned out the Condensate pipe was frozen, three kettles of boiling water later I have a perfectly functioning boiler again. Thank you for the forum and those whose post up the answers. I hope my answer will help others in resolving their boiler problems.
Jeeves (Leicestershire)
January 2010
read recent posts for worcester boilers - think us contributors have covered most bases relating to this
fault EA has a number of reasons - again read recent posts regarding manual for service engineers if u want further info and diagnosis - dont be put off its pretty straightforward and can help us to advise
eddie
January 2010
frozen condensate pipe.
apply warm water to the condensate pipe out side.
press reset botton for 10 sec
Steven B Riley
January 2010
think EA is no flame detected
b
January 2010
I can answer this question...