Sime friendly format 80E Intermittent Relight?

I have the same problem as Neil Johnson. Switch on and runs fine, when the temperature has been reached the burner shuts off as normal but sometimes does not relight when it should, turning it off and then back on relights the boiler every time. The problem has got progressively worse over the last twelve months, sometimes it will run fine for weeks and other times you have to relight ten times or more doring the course of a day. I assume the temperature sensors are ok because the fan is being restarted so I am assuming the PCB knows its time to relight. I am guessing either PCB or Ignition control box but am reluctant to gamble due to costs. Help!!

Christopher James
November 2005
you are right the pcb next to the gas valves is your problem, remove the pcb and with an eye glass check all the solderd peaks and i mean all! carefully and you will find about 15 dry joints [cracks around the peaks of the solder ] it took me 18 months to find this problem but i re solderd mine and bobs your unckel it is now back to normal, it would seem that i am the only guy that knows about this repair, do not give in, the main number of cracks are around the relays and back to the main chip on the pcb,the large resistor at the back of the pcb will get hot ,its normal for it to get hot,i now know this 80e boiler inside outi spent days working out the problem,even sime dont know,they and other boiler repairers say replace the pcb at a cost of £78.00,stick at be carefull and safe and you will win. bob rob.

bobby rob
May 2006
I have answered my own question as I seem to have solved the problem. See answer In Neil Johnson "sime friendly format 80E"

Christopher James
November 2005

Automatic Answer

We may have found other answers which could help you.

Click here for Friendly Format 80e Problem

Related Questions ...

Mend central heating diverter valve radiators
1

Sime Friendly Format 80e, replaced diverter valve but rads. still get hot?

Boiler: Sime Friendly Format 80e Problem: Radiators get hot when DHW is run. I had assumed this was the di... [Read more]
Mend boiler heating ignition
11

SIME FRIENDLY FORMAT 80E WONT FIRE UP???? PLEASE HELP!!!!?

the boiler is set to turn on via the timer which it normally does without any problems in the morning.during t... [Read more]
Mend boiler thermostat overheat
1

Friendly Format 80 E Gas Council Number 4771907?

my sime friendly 80e installed feb 2000 worked only one year,and always problem,the question i got it works fo... [Read more]
Mend friendly sime combi
1

whats wrong with my friendly format sime 80e combi bolier?

hi woke up today boiler not well any ideas what could be wrong? heating works fine,however problem with water ... [Read more]
Mend boiler central heating radiators
1

Sime friendly format 80E?

Myboiler when in central heating mode will heat the radiators until the set temp is reached then trip out as i... [Read more]
Mend combi boiler no hot water no ignition
2

How can I fix my SIME Friendly Format 80E Combi?

The situation is this: No hot water, no on light! When hot tap is opened there no flame, no fan and the pre... [Read more]
Mend boiler heating restart
3

problem with sime friendly format 80e?

boiler runs for about 15 to 20 mins o.k after it stops for a rest the boiler restarts for about 5seconds then ... [Read more]

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Home Heating Systems ...