5 hours ago: Trayford close coupled toilet?

Mend Saunier Duval Convector Heaters

Mend Heating, Convector Heaters
Find out how to mend it for free.

Ask Question
Mend Heating, Convector Heaters
Mend repair fix Saunier Duval convector heaters

Mend > Convector Heaters

Mend Heating, Convector Heaters

pressure variations on thermaclassic f30e combi?

i put pressure to 1.5 bar , turn on the heater , the pressure rises to 2. 5 bar and the safety valve lets by , , i have replaced the safety valve, when the boiler goes off , the pressure drops down to around 0.6 -0.8 bar , where the red fault lamp comes on, an the boiler wont restart untill i increase the pressure through thefilling loop valve, i have put a jar under the discharge pipe outside an get just under half a pintof fluid. can you help. saunier duval thermaclassic f30e faned flue combinationboiler

chris lane
April 2008
This is usually a sign that the expansion vessel inside the boiler has lost its air pressure...they are refilled using an ordinary car tyre pump to around 10 psi - or whatever the maker recommends.

John
April 2008

Automatic Answer

While you wait for answers, we may have found some information which could help you.

Click here for Pressure Combi Rises

Mend Heating, Convector Heaters
Mend repair fix Saunier Duval convector heaters

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Convector Heaters
Mend repair fix Saunier Duval convector heaters