glowworm swiftflow combi turning off and on?

my swiftflow combi turns itself off for a short time when taking a shower this can happen 2or3 times during the shower as you have to wait for the water to warm up again. Its much worst in the summer when the cold water supply is naturally warmer. During winter weather it may not happen at all any help appreciated.

jk
June 2005
It sounds as thought the domestic secondary heat exchanger is choked up, not allow sufficient flow from the main heat exchanger and therefore causing the primary water to oveheat. This shut down the burner and when it cools, it fires agaiThe only solution is to fit a new plate to plate domestic heat exchanger. They are available at keeptheheaton.com. Usually around £100. From: chris@higginsheating.co.uk.

Chris Higgins
March 2009
I had the same problem. Almost certainly related to the flow switch. In my case it seemed the water pressure was not quite enough to keep the flow switch open. I could prove this by partially opening a hot tap while I had a shower - it would solve the problem but obviously waste heat and water.

Solution in my case was simply to open the input tap a tiny tiny amount, to speed up the water flow slightly. It's easy enough to locate with the boiler manual and easily adjusted with a screwdriver. I had to open it really the tiniest amount I could. If you open it too far, water will flow too fast and won't really be hot when it comes out.

Good luck!
-Mark

Mark Smith
November 2005
have a look at the flow switch this is located at the cold water point of entry. it is a brass fitting with a ball bearing inside, as you open your hot tap this causes the bearingto carry to the top of the valve with water flow. when it does it causes the magnetic reed switch located on the outside of the valve to make a circuit. you can put a multi meter on both wires and you should get a complete circuit when you open the hot tap.
They can get worn and they have a circlip inside to retain the ball, ihave often found the clip broken and jamming the ball.
Angus

angus
September 2005
we have the same problem - in winter in Canberra, Australia
Sorry I don't have an answer!

aw
July 2005

Related Questions ...

Mend heating thermostat combi
1

ideal combi 30 boiler heating not working on timer only override?

The heating only comes on when I override the timeclock if in timer mode the timeclock keeps the correct time ... [Read more]
Mend combi boiler heating overheating
1

FF 14 extra fast combi boiler?

My extrafast 96 will deliver DHW on a moderate flow but cuts out after few seconds on full flow from a single ... [Read more]
Mend rid air system
2

How can I get rid of trapped air in central heating system?

After replacing the small rubber seal on the shaft of the hydraulic actuator in my BIASI 24S Combi boiler, the... [Read more]
Mend combi heating faulty
1

Main combi boiler ?

Why is my boiler sending hot water to my radiators when I only want hot water to my taps. The heating is turne... [Read more]
Mend boiler sealed system hot water
1

Grant outdoor combi 90 v3?

My sealed system loses pressure when I run the hot water. When boiler cuts in the system builds up pressure ag... [Read more]
Mend combi heating pressure
3

baxi 105e combi boiler?

boiler wont modulate when central heating is on causing pressure to exceed 2.5bar, is it the electric safety s... [Read more]
Mend combi-boiler heating fault
3

Sabre HE Combi boiler fault?

Hi, I've got a two year old Sabre HE combi-boiler. The heating and hot water is now not working. The green lig... [Read more]
Mend boiler heating combi
1

water pressure?

I have had a plumber(SAFE REG) to change 2 pressure values thinking the 1st was faulty but it is still the sam... [Read more]
Mend boiler fault thermistor
1

Hi i have a britony combi se coming up with 50, 70, 80!?

Hi i have a boiler fault which is flashing 50, 70, 80, checked the fault finding guide which says central heat... [Read more]
Mend combi pcb modulation
1

help help help?

Please someone help we have had about 4 heating techs out all safe gas registered and no one can help its cost... [Read more]
Mend combi diverter valve central heating
1

how can i fix my vokera maxim combi boiler?

my combi is about 12 years old, but lately it has been cutting out when the central heating and sometimes the ... [Read more]
Mend boiler pressure relief valve
1

ideal combi pressure loss?

when i top up my ideal 280 combi to 1.5 bar water is passed outside via safety relief valve.the pressure go,s ... [Read more]
Mend boiler leak system
3

Combi boiler – faulty pressure gauge or water leak?

I don’t know if my combi boiler and system (a) has a water leak or (b) just has a faulty water pressure gaug... [Read more]
Mend ideal boiler ignite
1

My Ideal Mini C24 Combi Boiler wont ignite?

Last night the boiler was working ok, went to switch the boiler onto constant this morning only to find that i... [Read more]
Mend boiler pressure heating
1

Heating, Home Heating Systems?

My Worcester Bosch combi boiler loses pressure over 24 hours from 1 bar down to almost zero. The boiler still... [Read more]

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Home Heating Systems ...