1/ Are all three Rad's in series or parallel ? If series any one valve being closed will stop all 3 !
2/ Can you isolate the temp. control valves ? If so strip the top ( bellows ? ) portion, slowly return water to line while checking for leakage and then open the control valve manually; press down or pull up as appropriate. This will tell you if the blockage is truly at the control valve or elswhere.
3/ If it's the valve most manufacturers will supply repair kits; beats taking the valve body out of the line and fixing subsequent leaks.
GMR
November 2007