Mend Worcester Combi Boiler Pressure Home Heating

Expansion vessel recharge?

I've noticed recently the pressure on my 1.5 year old Worcester combi boiler has been going through the roof whenever the heating comes on. It goes to around 3.5 bar, having been set at 1.5 when cold. I reckon the expansion vessel needs recharging - is this something a competant DIYer can do? Is there a way of checking that it actually in need of charging?

I'd include more details of the boiler but I was late for work this morning when I noticed the rather alarming pressure...

James
May 2007
how do i know how much air to put in?

JD
February 2012
An hour of fun indeed,But now a perfect pressure and no more annoying top-ups,thnx all for your input....

paul
May 2007
Logically the only way it would loose pressure is through a leak, either directly to atmosphere or through a ruptured diaphragm to the water (and hence through the automatic air bleed to the atmosphere). Assuming the vessel has no leaks then the car tyre type valve (Schrader (sp?)) could be faulty, you could replace the core with a new one. There should be a decent valve cap on the valve with an 'o' ring to seal against the lip of the valve, so that if the core isnt perfect air still cant escape. Perhaps the cap is missing and dirt has got into the valve. FWIW I find it odd that such a young boiler has this problem, but am not an expert, I cant see how draining and refilling the system would make the expansion vessel loose pressure.

c
May 2007
Incidentaly - do you know why an expansion vessel would run out of pressure.... I have been just moved a radiator recently, so the system has been partially drained and refilled a few times.

J
May 2007
Exactly what I needed to hear - thanks so much for taking the time to help. I'll have a go soon and let you know if I need any more help.

Thanks very much

James
May 2007
Yes you can do it. I dont know your specific boiler but the expansion vessel is behind the boiler and has a car valve type connector at the top. This is where you can connect a car tyre type pump/guage.

With zero pressure in the water system (front panel guage - you can probably let the pressure off by manually lifting/twisting the over pressure relief valve, or opening a bleed point on a radiator (v messy)) you will need 12 or 15 psi in the vessel (check your manual).

Before the pressure starts to build in the vessel you will need to displace around 8 litres of water (vessel specific)from the vessel through the over pressure vent or the bleed point, only then will the pressure start climbing, it takes a lot of pumping.

I do not know how reliable the expansion vessels are in your make, check that the vessel isnt faulty first by pushing down the central pin in the valve, if damp air with a little moisture comes out it is OK, if water squirts out it needs replacing, not recharging.


After recharging refill the system up to the top of the working pressure range, (1.5 bar?) turn the CH on and check that all is well. Recharging the vessel may also cure any need for frequent small water top ups.

While the system is at zero pressure it may be a good time to inject some fernox system protector maintanance gunk with a caulking gun at a bleed point, the adaptor supplied can be usefull when letting out the initial system pressure too. If you have any small leaks you could try giving it a shot of fernox leak sealing concentrate stuff as well.

An hour of fun for a wet Sunday afternoon.

c
May 2007

Related Questions ...

Mend boiler heating pressure
1

What's wrong with my Worcester Bosch 24i Junior Combi Boiler?

Hi, I've come home today to find I have no heating/hot water and a boiler that I thought had a frozen condense... [Read more]
Mend heating pressure worcester combi
2

home heating?

the pressure increases up to 4 on my worcester 35cdi2 combi boiler when i turn the heating on what,s wrong?
Mend combi heating boiler
1

Baxi Combi 130 HE?

My boiler is driving me mad please help! When i switch it up (which is ment to be ON) it isnt coming on, and t... [Read more]
Mend boiler pressure heating
1

Heating, Home Heating Systems?

My Worcester Bosch combi boiler loses pressure over 24 hours from 1 bar down to almost zero. The boiler still... [Read more]
Mend boiler heating combi
1

home heating system?

we have a vokera compact 28 combi boiler that keeps losing pressure, and the overflow pipe outside is constant... [Read more]
Mend water problem going
3

No water in hot water tank?

Hi there, I have a problem... lol I'm afraid I'm going to err on the side of giving too much information... [Read more]
Mend combi heating pressure
1

Ravenheat RSF 84ET - not heating rads or water?

Good Morning guys, I am looking for some advice regarding my girlfriends Ravenheat RSF 84ET combi bo... [Read more]
Mend combi boiler leaking pressure
2

My Worcester 24CDI combi boiler leaking brown sticky fluid badly!?

Hello all, Hope someone can answer my question as I am quite concerned. I have a Worcester 24CDI combi boi... [Read more]
Mend boiler central heating hot water
3

How can i find out what is wrong and fix my ferroli combi boiler??

hi everyone! i have recently had a problem with my boiler at home, with it been winter its cold and my heat... [Read more]
Mend heating radiators combi
1

Alpha CB24 Combi Boiler not heating up radiators?

My home radiators are not heating up enough to warm the flat, the Boiler works fine, had the radiators cleaned... [Read more]

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Home Heating Systems ...