Recent: Fix food processor motor?

Mend Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Free repair help for home heating systems

Mend > Home Heating Systems

Mend Central Heating System Over

Why is my central heating system over pressurising?

Why is my central heating system over pressurising?
I woke up this morning to hear water running! on investigation I found that it was the pressure relief vlve on my central heating expansion tank letting off.
By this time the tank had drained to 0 bar so I re-set the valve and re-filled the tank to 2 bar and turned the water and heating back on. Within an hour the same thing had happened again, what is the problem? can someone please help?

Archie
December 2010
firstly 2 bar is too much pessure really it wants to be at about 1.5 when its cold this will creep up to about 2.1 bar when hot if pressure is still reaching 3 bar the expansion vessel has lost its charge and would need replacing as it allows for expansion in the pressure

aaron
December 2010

Automatic Answer

We may have found other answers which could help you.

Click here for Central Heating System Over

Mend Heating, Home Heating Systems
Free repair help for home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Free repair help for home heating systems