Recent: Fix food processor motor?

Mend Ariston Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Find out how to mend Ariston home heating systems

Mend > Home Heating Systems

Mend Ariston Pump Central Water

how can I set the pump overrun?

My central heating/hot water system. Ariston model dia system 27rff1 serial No: 971009407
with the central heating no problem. once the central heating go,s off the hot water system trips on high temp;

clive
February 2010
make sure a bypass has been piped into the system so the pump water has somewhere to overrun to

john
February 2010
sorry should havbe said that this is a requirement so if your sysstem has been recently installed notify your electrician or installer

adam dowsing
February 2010
you need a permanent live supply from the spur to the boiler which doesn't run through any of the stats or programmer. There should be a place in the wiring centre of the boiler for this marked or pump over run. You then need to mke sure the pump and boiler triggers are common to ensure the boiler can tell the pump to continue to run.

adam dowsing
February 2010

Automatic Answer

While you wait for answers, we may have found some information which could help you.

Click here for Pump Central Water

Mend Heating, Home Heating Systems
Find out how to mend Ariston home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Find out how to mend Ariston home heating systems