Worcester 9.24 Electronic BF boiler, pressure keeps dropping?

Hi my boiler keeps dropping the pressure, this happens straight after the central heating goes off and sometimes it just goes down after some time. this decrease in pressure causes the pilot light to go out. we normally have to put the pressure up twice. daily and put the pilot light on every 2-3 days. i think if i could sort out the pressure problem then the pilot light would stay on. after the central heating has been on, once the central heating water cools the boiler pressure drops very low-nil. also when the hot water tap is opended, the pipes vibrate and shake and the boiler flame is out. sometimes this can happen during use of warm water. please could someone let me know what the problem is and what i need to do to sort this out. this only happens during winter, during summer, the boiler is fine. also i have seen on the installation manual that the boiler has a summer/winter switch, but i dont know how this works and how to use it, maybe i could sort the problem out by adjusting this switch.

jack
February 2010
Hi Jack
i just came across your problem with your boiler did you fix it.
mike

mike67
February 2011
Yes before central heating is turned on, the pressure is just above 1 bar, but during central heating running, the pressure can reach 3 bars or sometimes max's out (max pressure), the water does flow out of the releife pipe. Where can i get a eplacement pressure vessel, or how can i recharge the old one?

Jack
February 2010
sounds like most problems could be associated with a pressure vessel fault. You say when heating goes off (ch system cools) pressure is down.
If you noe top up to 1 bar and run central heating, what reading would read after say half hour an hour???
Will it be reading 3 bar +? Is it letting water out the relief pipe outside during this time?
If yes then pressure vessel fooked or flat and needing recharge.