Mend Sime Release Pressure E

How do you release pressure from the SIME Friendly E boiler?

Pressure should normally be between 1.5 and 2 bar. It's currently at 3 and water is overflowing from the system. Just need to know if there's a release valve.

Thanks

Bob
August 2008
Thanks guys radiator drain did the trick will now run for a while to check everything OK. Could have been the inlet was knocked to on as it's in one of those places.

Thanks again.

Bob

Bob
September 2008
hi andy from TOTAL BUILD AND HEATING you shold have A drine off on A rad some were in the house drine down to 1.5 bar jobs A good A

andy
September 2008
Your pressure vessel could be in need of renewal. Robin is correct about releasing pressure, but you can cause p.r.v to let buy.you can also release pressure through venting a rad into a jug.

Tony R
September 2008
Just trace the discharge pipe (that goes through wall for overflow/overpressure) back up under the boiler. You will find a brass block with (usually) a red knob. This is the pressure relief valve. Slightly turn and hold the knob anticlockwise to discharge. If the boiler is contantly at 3 bar and discharging all the time check that the filling loop has not been left open or that the shutoff valve is not letting water by.

Robin S
September 2008

Automatic Answer

While you wait for answers, we may have found some information which could help you.

Click here for Release Pressure E

Mend Heating, Home Heating Systems
Free repair help for Sime home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Free repair help for Sime home heating systems