Migster, you are a lifesaver!
For anyone looking for Migster’s post, here’s what he had to say, and it works!
“I had the same problem with my ariston bioler after bleeding the radiators (removing the air from them). From what i can see the "E 02" code means a lack of pressure in the system.
To clear this i released more water into the system on the MFFI boiler there should be 2 black taps on the inlet pipes turn the middle one about half turn. And then slowly release the left hand side tap to release more water in to the system .
!!!!! be very carefull not to over fill.. once the system is hot the preassure will be build do not exceed 1.5 bar !!!
i got my system working doing this.. but i would advise getting the boiler checked by a corgi engineer.”
Tony
March 2015