if your pump is turning and the flow switch is working (you can test this by following the flow switch wire to the pcb then short the conection out across the terminals on the pcb its low voltage) and the fan runs ok and the diverter valve is opening and returning ok the vacum switch (air pressure switch) is droping out, test it by pulling the tube off it and blow and suck on it if the boiler lights with that, change it but check the tubes are not blocked to it :) have fun they can be a pig even for proffesonals
Brian the heating engineer :)