the optima xm does not have seperate tampers for each zone there is just one tamper so is it a tamper or is it zone 3 coming up i would imagine it is zone 3 becuase if it is a tamper the alarm would lock up and be unusable
if linking it out at the panel works then the panel is ok try linking it out at the join you made (the end that comes from the panel. if that works you have proved 1 you have the correct cable and that it is ok connect back up to the wires thought to be coming fro the door switch (contact) if not working link out at the door switch contact as it could be a faulty door switch(contact) if still not working then i would say that is not the cable you think it is or i is damaged really yo need a mtere so you can prove the cable to be the correct one and ok
Chris AXIS Fire & Security
March 2007