You have a combi boiler?
Burner doesnt stay on for heating & hot water?
You can hear a fizzling noise from the boiler when on?
Like a kettle boiling?
You have sufficient water pressure?
Indicated by water pressure gauge on boiler
All radiators have been fully bled/vented?
FLOW & RETURN temperature differentials within manufacturers specifications?
Burner gas pressure within manufacturers specifications?
Pump operating correctly?
Not seized
From the limited information you have provided
I would say the boiler is overheating & cutting out on the
High limit temperature stat
Why is the boiler overheating?
Would need to do additional tests to determine cause eg
Temperature differentials
Burner pressure
Gas rate
Flue gas analysis
System water quality analysis
Derren brown