Mend Glow-worm 24CXI Boiler Heating Glowworm

glow worm 24cxi boiler?

f5 code I pressed the red button but it keeps on tripping.
its happened since I had another rad fitted.

waz
April 2015
the f5 is that the boiler is sensing it is getting too hot - usually that the water is not taking enough heat away from the boiler. It could be that the flat-plate heat exchanger is partially blocked. You could try a quality cleaner, or take out the heat exchanger and give it a good flush - a bit awkward but worth the 20 minutes if you are competent.
If f5 occurs only when the central heating is running, it may be silted pipework - the pump not running efficiently (try turning the pump up to no 3 if it has a speed control.) Is the pump running at all? - you should hear it running. Try turning down the heat control on the boiler - does it still trip with the F5 fault code. A good gas engineer should sort it quickly, though there are others who have the qualifications but haven't a clue about fault finding and will just keep replacing parts until they strike gold. (your gold unfortunately!)

Mike Whalley
June 2015

Automatic Answer

We may have found other answers which could help you.

Click here for Boiler Heating Glowworm

Related Questions ...

Mend boiler ignition fault
1

Home heating systems?

I have a Glowworm 100f gas boiler system It has a fault where the ignition stays on when the pilot light is l... [Read more]
Mend combi boiler central heating radiators
1

why is my combi boiler not staying fired for central heating. water fine?

my Glow worm combi has been having odd days when the central heating isn't working but then has been ok again ... [Read more]
Mend gas boiler thermostat hot water
2

Glowworm cx30i gas boiler?

My boiler comes on intermittently when the thermostat is turned down below zero degrees. It is all running fi... [Read more]
Mend boiler pressure engineer
1

New glowworm ultimate c 30 boiler losing pressure?

We have a new boiler about 8 months old but have been using it daily for about a month for heating. For the fi... [Read more]
Mend boiler heating engineer
2

What is wrong with my boiler - hot water only occasionally, heating fine?

I have a Glow worm Betacom 30c which I'm not impressed with due to the unreliability of the hot water. The ... [Read more]
Mend 30 problem heat
2

glowworm betacom 30 problem?

Hello folks, boiler is 2 years old, had plate heat exchanger cleaned/changed/cleaned...dhw sensor replace... [Read more]
Mend boiler pressure heating
2

pressure on glowworm 30ci?

my boiler keeps losing pressure and drips every so often i keep building the pressure back up, the only way th... [Read more]
Mend boiler central heating lockout
1

Boiler fired but cuts off (Glowworm Micron 60FF)?

My boiler has suddenly stopped working. When it is reset, it starts the fan, and begins to spark presumably (a... [Read more]
Mend boiler heating noise
1

How do I fix my Glow worm compact boiler?

My boiler makes a buzzing noise when switching on my central heating. Hot water works fine. No central heating... [Read more]
Mend boiler central heating fault
1

Glowworm Flexicom F1 F4 faults?

Having a problem with boiler cutting out. NOT a condensate problem. Key bit of information is that it will run... [Read more]
Mend central heating boiler glowworm
1

boiler will not turn off?

glowworm hxi boiler is constantly pumping hot water to central heating circuit even when the external programm... [Read more]
Mend heating boiler repair
2

glowworm betacom 30?

Does anyone know how to fix the error 60 (bar with a downward arrow) on this boiler. Have tried turning it ... [Read more]
Mend boiler heating glowworm
1

glowworm 30 ci temp raises rapidly?

temp on boiler gauge rises rapidly but heating never gets hot
Mend central heating heating system glowworm
1

central heating only comes on when the hot water heats?

I have a GlowWorm Micron 60FF boiler..the central heating only comes on when we have the hot water on.Which me... [Read more]
Mend boiler fault hot water
1

heating not working. glowworm 18hxi?

two of my radiators have not been heating up, yeaterday i switched the rest of my radiators off bar one to see... [Read more]

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Home Heating Systems ...