Recent: Fix food processor motor?

Mend Potterton Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Free repair help for Potterton home heating systems

Mend > Home Heating Systems

Mend Potterton Starts Hw Ch

Potterton Profile 80E Starts OK on HW but not on CH?

Boiler would start (fan running for 20 seconds) but would not complete the ignition cycle. Replaced the PCB. After replacing the PCB the boiler goes through full start sequence and ignites when programmer is set for HW only. When progammer is set to CH nothing happens; no start up at all. Replaced the programmer with new unit but same problem. Replaced room thermostat but still the boiler will not start when programmer on CH. Circulating pump is one year old.

Mike Newbury
May 2012
CH valve is closed change motor in diverter valve,power is transfer from diverter valve to boiler

ltd
May 2012
Mend Heating, Home Heating Systems
Free repair help for Potterton home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Free repair help for Potterton home heating systems