will prob give u an ignition fault code on boiler if condensate problem, there may be a sensor in the condensate trap that got wet due to it freezing at some point and backing up into boiler. sounds like a very poor install, the pipe should be constantly falling- ie no straight runs, also it sounds like it just terminates outside into nothing? it should go into a waste pipe or a purposely made soakaway pit with limestone as the condensing product is very acidic. also should be minimum 32mm diameter pipe if any external runs (unheated garage also classed as external) the fact that u scraped out something that wasnt liquid points out that it was defo blocked at some point. u can google trace wire heater and get something installed similar to it, basically a heat wire run through the pipe that comes on if temp drops below 5'c, if u know a sparky or competant u could get one, dont know how much they cost though. if installed recently- get them back as it hasnt bn installed as per installation instructions. hop this helps
billy
December 2010