How can i stop a constant flow of water coming from my outlet on my combi ?
The bolier is a Ariston combi approx 3 yeras old.There is a constant flow of water coming out of the overflow.
There is an additional problem, when any tap is turn on you can here one of the radiators making a noise.
Water flow out of the boiler means that there has to be water flow in - so make sure that the filling loop is fully off. You may need to replace the PRV as they often don't seal properly once opened. See if you can maintain boiler pressure at about 1 bar.