VAILLANT BOILER (COMBI) F. 1 FAULT, INTERMITTANT HOT WATER?

Hi, we have a Vaillant Combi boiler, about 7 year or so old, it keeps coming up with the fault F. 1 this means if your having a shower it warms up but then after only a minute if that goes stone cold, if you leave it the fault won't go away unless turn boiler off for 10 mins or so, but now even that doesn't work always, it sounds when first turn on as if a pump or something is trying to start up, about three drone noises in a row.

When it's working it's great & would keep working all day if don't turn water off, but more often than not once waters turned off F. 1 fault comes back.

Pressures correct & I've even drained & refilled the system, but still no joy, PLEASE HELP ;0)

Steve (Rugby/Warwickshire)
June 2009
Thanks RR
I will speak with my local Pump centre to see if they can throw any light on what your saying, seems odd the lack of knowledge around this F. 1 fault.
Cheers
Steve

Steve
July 2009
Not knowing the combi model ?
F 1 is probably the return NTC open circuit.
NTC broken,NTC cable broken, poor connection at NTC or at connection to the electronics.

RR
June 2009

Automatic Answer

We may have found other answers which could help you.

Click here for Vaillant Boiler F Hot Water

Mend Heating, Home Heating Systems
Click here to mend Vaillant home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Click here to mend Vaillant home heating systems