Boiler pressure will not increase, please help?

Hi,
I have a combi boiler which has a low pressure of 0.9 the boiler only works sometimes and takes a long time to fire up. I have tried increasing the pressure by the usual method but there is no hissing sound and no rush of water and the pressure does not budge. Water also escapes from the top valve when I open it. Any ideas why this is? Thank you

Suzanne
January 2009
You sound like you know what you're doing - are you using a removable filling loop? If you are it may well have a one way valve in it to stop heating system water flowing back into the mains supply (I know this shouldn't happen because mains pressure is higher than your heating system pressure - but they have to play safe) Try putting the filling loop back on the other way around and see if water flows properly - I think it might!
If you DON'T have a removable filling loop then it sounds as if mains water is unable to access your system - look for a valve/isolator that may have been shut off and will need opening to allow flow.
Good luck.

Richard
January 2009

Automatic Answer

We may have found other answers which could help you.

Click here for Increase Help Low

Mend Heating, Home Heating Systems
Mend repair fix home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Mend repair fix home heating systems