Mend Ferroli OPTIMAX 25C Boiler Fires Seconds

FERROLI OPTIMAX 25C OVERHEATING?

When I turn on the hot tap the boiler fires up then a few seconds later it overheats and I get F3 fault code, the pump is running and it has a new flow sensor as this is what the fault finding guide stipulates, I have noticed that the diverter valve was switching to heating when hot water is demanded and hot water when heating is demanded, the diverter valve has also been swapped to see if it was that but still the same fault, the pcb has also been test swapped and so has the hot water flow meter still to no avail! any advise would be greatly apreciated :)

Adrain
January 2009
My boiler pressured right up to plus 4 bars I drained the rad bk down to 1.4 I have no hot water or heating and it's trying to fire up but not ignighting any ideas !? Then the fault comes one to f1

Sam
February 2014
Hi.
Has anyone got the pcb settings for the optimax 31c?

Vtang
October 2013
Hi, you need to reprogram the new PCB with the25C settings. Had the same problem myself, the diverter valve is going to CH when the hot tap is opened causing the chamber to overheat and bang.
The Settings are:
P1-00
P2-06
P3-00
P4-00
P5-07
P6-02
P7-80
P8-04
P9-20
P10-60
P11-00
P12-28
P13-80
P14-85
P15-04
P16-10
P17-20
P18-57
P19-10
P20-15
P21-25
P22-10
P23-80
P24-40
P25-00
(Settings obtained from my old PCB)
Use the power and M button to enter the set up and the radiator dial to adjust.
Hope this helps.

Ryan
December 2010
did Adrain fix his boiler in 2009 if so what did he change mines doing same 03 fault diverter valve going to heating when you call for hot water and pump gos off it bangs a bit then gos off could it be p c b or do i need a new boiler

tony
April 2010
how do you reset the parameters please

dave
August 2009
Hi i would love to no if you have sorted this problem as i have the same boiler and i have the same problems, mine makes a banging and clunking noise f3 comes up when my hot water stops runs for 5 sec then (d) come up,then re set it self and i have no ch, can anyone help me please paul (ps) some one did say it was the diverting valve, reading this one i am not to sure?

paul
March 2009
If you've changed the control PCB you will have to reset the parameters. PCB are set for system boilers so it will o/heat and make all sorts of banging noises b4 F3 comes up.

Gasser
February 2009
The fault lies in the pcb that sits under the gas valve. Is this the pcb that has been test swapped ? Swapping the display pcb won't help you.

Richard
January 2009
have tried fitting a new safety thermostat.
it could be that the pump over run setting needs adjusting.

phil
January 2009

Related Questions ...

Mend heating boiler Worcester Bosch
1

Boiler cycle?

My boiler only fires up for about 90 seconds greenstar 4000
Mend boiler hot water system failure
2

hot water home?

boiler fires up for a couple of seconds and then shuts off, no hot water
Mend boiler combi boiler home heating
1

baxi105he combi boiler?

the boiler fires up when you call for ch the boiler runs for a few seconds then goes out
Mend boiler heating reset
3

boiler won't fire up?

after pressing the reset button, the boiler fires up for just a few seconds, then switches off again
Mend boiler lockout glow-worm
1

boiler lock out glow worm beta com 30c?

boiler locked out pressure at 1.5 bars. condenser sensor is dryer. no water in condenser or pipe.boiler fires ... [Read more]
Mend boiler potterton performer
1

potterton performer 24?

boiler fires up then goes out for 10 seconds then fires up again
Mend boiler heating hot water
1

how can i fix Ariston micro Genus 23MFFI?

I have an Ariston micriGenus 23MFFI boiler.When i want hot water or heating the boiler fires up and runs for a... [Read more]
Mend boiler fault heating
2

Suprima 50 HE No lights unless Gas Valve disconnected?

Hi, I have a Suprima 50 HE boiler that decided to stop working yesterday. When I got to it, all 3 lights w... [Read more]
Mend boiler central heating pcb
1

Procombi 85 HE hot water ok, but central heating not working?

The boiler is working when I run hot water, it fires up when the central heating is turned on, the pump get's ... [Read more]
Mend heating pressure reset
1

The pilot light on my boiler keeps going out?

I have always had a problem with my ferroli boiler. when I turn my heating off and come to turn it back on aga... [Read more]
Mend heating pipes water pressure
1

loud bag noise for few seconds till the boiler fires up,?

First thing in the morning when i switch the hot water on i get a loud bag, sound like air in the pipes. I hav... [Read more]
Mend ravenheat pcb central heating
1

my ravenheat rsf 84 et boiler?

can someone help me my reavenheat rsf 84 et boiler when you turn on the hot water the boiler fires up ok then ... [Read more]
Mend heating pressure boiler
1

how can i fix my biasi boiler?

my boiler fires up but keeps cutting out after about 15 seconds, I reset the boiler but cuts out again. the wa... [Read more]
Mend boiler pressure heating
1

boiler making a funny noise like bubbling water then switches off?

my boiler is a charcuterie and Marist model and it fires up after 5 seconds or so of makes a strange noise and... [Read more]
Mend Saunier Duval Combi Boiler Central Heating
1

No c/h working saunier duval f23e combi boiler?

hot water working fine but when turning the central heating on it fires up for a few seconds and then switches... [Read more]

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Home Heating Systems ...