fault diagnosis?

worcester 28cd1 boiler drops pressure daily to 0.5 and requires daily topping up, have checked and found no leaks is pressure vessel at fault

n j north
January 2009
the boiler is displaying ea and not working what can i do to fix it?

tony
December 2010
worcester bosch boiler cutting out saying ea on display panel pilot light cutting out

andy
January 2009
Unless your system pressure is also getting very high (3bar) when hot then the PV is probably ok. The pv is designed to accomodate the increase in pressure so it should go up from say 2bar cold to 2.5bar hot. If it starts at 1.5bar cold and goes up to 3bar hot then the pv is not working and needs re charging or replacing. Don't forget there is a presure relief valve in the system and the seal on this can fail causing a gradual leak and so loss of pressure. Good luck

Richard
January 2009