Mend Boiler Disconnected Reconnected

Increase pressure in Ideal C95FF combi boiler?

We recently disconnected a radiotor before decorating, but once it was reconnected and the valves opened again the pressure indicator on the boiler dropped to 0 psi and now there is no heating operational. Hot water works fine. How do you add pressure to the heating system with this boiler?

Gareth
September 2008
from TOTAL BUILD AND HEATING do you have A filling loop on boiler if so just open and fill to 1.5 bar plus make sure all rads i.e vants are open to let air out 1 at a time plus keep toping up boiler when doing this untill you have 1.5 bar MINT HAY

JUSTTO GOOD ANDY 20 EXP
September 2008