Intermittant hot water on Baxi 105e but heating OK?
Hi,
My Baxi 105e combi only gives hot water when I run the bath (and that's happening less and less - can't get any from kitchen/bathroom sink) or have the central heating on.
quote T: (could be scaled up and require cleaning or need a new diaphram)
thats definately where i would start observing to see if the taps that do not work can make the microswitch. if not could be diaphragm, scaled up pin or blocked impulse tube
iain
June 2008
there is either a problem with the dhw flow sensor (could be scaled up and require cleaning or need a new diaphram) or the inline main water filter under the boiler could be partially blocked