Same problem with Space Saver 40B Mk11.
I have replaced..thermocouple, thermocouple connecter lead, pilot burner, and gas valve. All worked well after replacing gas valve, but only for six weeks.
I have since replaced the thermostat and pump and power flushed the complete system.
All the above work was done by myself at a total cost of...£408!!!
Today I took out the flue and cleared a few leaves etc from it..but it made no difference.
However, if the seal between the wall sleeve and the outer flue has the slightest bit of a gap between them, this may cause oxygen deficiency.
I have this evening re-sealed the 'gap' with some fire cement and believe it or not...all is well!
Although I only have the thermostat on its lowest setting, I am now sitting here monitoring the system and all appears to be spot on!
I have requested advice from this forum on numerous occasions, but eventually sorted it out MYSELF!!