Recent: Fix food processor motor?

Mend Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Click here to mend home heating systems

Mend > Home Heating Systems

Mend Pressure Boiler Bar

Pressure problem on vailant 630 ecotech plus?

Hi I have a Vailant 630 system boiler and the pressure goes up to maximum 3.3 bar and im force to take water out from the radiator to decrease the pressure, I just changed the expansion vessel and pumped it before conecting it to 12 psi as per instruction I have also changed the pressure sensor, as I said I set the pressure initially at 1.3 bar after few hours it reaches 1.9 and the following day is at maximum 3.3 bar. Can someone please advise what to do, many thanks

Darius
December 2010
Assuming you have re-charged the expansion vessel correctly (including leak testing the Schrader valve after charging), I suggest setting the system pressure to the correct level and completely disconnecting the filling loop. it may be slow filling if the valves do not shut off completely.

Carefree
December 2010

Automatic Answer

We may have found other answers which could help you.

Click here for Pressure Boiler Bar

Mend Heating, Home Heating Systems
Click here to mend home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Click here to mend home heating systems