Mend Glow-worm Ultimate 70FF Boiler Programmer Valve

Stuck wiring glow worm ultimate 70ff boiler?

I have a glow worm ultimate boiler and my system is a Danfoss heatplan pack with programmer and (2 x 2 port valves) the heatplan wiring looks straight forward, but confused with boiler looks like the boiler needs L,N,E + single pump supply wire, also mentions a permanent live to boiler but looking at it i think not required??? the confusing part is the 9-SL connections in the boiler it says take out the red link, what connects if anything to them??? or do i put the link in??
any help would be great

Rob

Robbai
May 2009
Permanent Live ... a permanent Live
SL= Switched Live, this is the Feed to Start the Boiler
PL= Pump Live, the Circulating Pump must be fed from this terminal.

The reason is that the Ultimate is a Low Water content Boiler, which has the need for the Pump to continue to operate after the boiler has shut down.

Hence the PERMANENT LIVE and PUMP LIVE. these two connect to enable the pupmp to over-run controlled by a thermostat in the boiler

www.elanar.co.uk
May 2009
i think external controls go in where the link comes out.
like the room stat or live that come from your wiring center

b
May 2009

Automatic Answer

We may have found other answers which could help you.

Click here for Boiler Programmer Valve

Related Questions ...

Mend boiler programmer pump
1

ideal w rs460?

Hi there' im a electrician and have been asked to replace a programmer for this boiler ideal w rs460 which wa... [Read more]
Mend boiler heating thermostat
1

combi oil Worcester greenstar heatslave 12/18 switches off?

I have a internal combi oil Worcester greenstar heatslave 12/18 Its has a built programmer and Hot water t... [Read more]
Mend heating boiler diverter valve
1

He 30 ISAR boiler heating coming on when not set to?

My ideai he 30 boiler is set on timed but continually keeps coming on when not suppose have had new diverter v... [Read more]
Mend boiler heating pump
1

Y Plan - Mid Position Valve 'fault'?

Hi, I have BGMVSP-23 'mid position' valve. (I believe a Y plan setup) Basically the pump only runs when ... [Read more]
Mend boiler central heating hot water
1

potterton ep2001?

'central heating' kicks in on all settings but the 'hot water' only settings fail to fire up boiler. Is it lik... [Read more]
Mend boiler home heating ignition
3

my protherm 40-50ci boiler blows fuse?

my boiler fan runs and gives a constant clicking noise but fails to ignite then blows the 3 amp fuse on the fu... [Read more]
Mend heating valve programmer
3

No HW but HW+CH works fine?

Hi Just bought a new house but got problems with the hot water. When I switch both HW+CH everything's ok. I... [Read more]
Mend boiler heating replacement
1

New replacement Netaheat profile pcb not working?

What is the problem my new replacement pcb will now not work without me banging or jolting it then it sparks u... [Read more]
Mend heating thermostat electrician
2

Broag remeha 24v boiler working perfectly -but?

The boiler fires up when it should with the programmer, everything fine until programmer times out but electri... [Read more]
Mend drayton room heating
1

drayton wireless room stat?

I have a drayton wireless room stat controlling the heating. the boiler is an ideal icos. The trouble i hav... [Read more]
Mend boiler heating vaillant
1

Problem with my Vaillant eco tech 428?

I have got a Vaillant eco tech 428 heat only boiler which has been installed to a pressurised heating system. ... [Read more]
Mend thermostat heating voltage
2

How do you fix intermittent heating problem?

I have a new Salus programmable thermostat (RT500RF) and a new Bosch Worcester Greenstar 24Ri boiler. Sometim... [Read more]
Mend boiler heating motorised valve
1

Potterton Suprima - continually runs!!!?

Hi, My boiler ha started to run continually. My only way of controlling it is to switch on or off by the wall ... [Read more]
Mend central heating hot water valve fault
1

Mid way valve fault??

I currently have hot water but no central heating When I move the 3 way valve to the H position manually the ... [Read more]
Mend central heating radiators thermostat
2

Central heating confusion?

I seem to only get hot radiators while my boiler heats my hot water but as soon as that get to temprature even... [Read more]

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Home Heating Systems ...