The boiler (ferroili optimax 25c) in the house which i'm renting has stopped working christmas day i've no hot water or central heating and the fault code is "F" 37 i can't get intouch with th landlord or get anyone to look at it until after the new year i have small kids which need the hot water
can anyone help point me in the right direction is it something i can do or do i need a technician.
I just followed spooks advice and it worked. Thanks!
NG
August 2009
ignore id**t above. system pressure on sealed system should be 1 bar when cold. anything near 3 and safety valve could discharge as well as leak out of any suspect pipework. system pressure gauge could be blocked. should be a silver filling loop that connects from cold water inlet on boiler to heating return pipe under boiler, open valve or valves slowly until pressure at 1-1.5 bar then reset boiler. if no good call engineer.
spook
January 2009
there's a few taps underneath the boiler is it the blue one ? do i just turn it and leave it ? is there any propper way i should do this ?
dandanuk
December 2008
cant fix it completely but i had the same problem. you need to repressurise the system. there should be a tap to release water into the system. you want it around 2.5 - 3 bar