Recent: Toyota overlocker model 3400 D?

Mend Vokera DVD Players

Mend Video, DVD Players
Find out how to mend it for free.

Ask Question
Mend Video, DVD Players
Mend repair fix Vokera dvd players

Mend > DVD Players

Mend Video, DVD Players

Why do I need to fill my system daily?

My boiler needs re-pressurising daily. I have checked the expansion tank @ 1 bar. I cannot find any leaks. I have installed liquid leak sealers into the system and I still have to fill the system every day.

It's a vokera linea 24 about 7/8 years old.

Bobby
October 2008
if its that old the diaphragm in the expansion vessel is probably ruptured, any water coming out of the schrader ( air ) valve.? if so it's knacked.( answer above is also correct)

richard ( heating eng'n'r )
January 2009
Unless you depressurised the radiators/boiler the expansion vessel pressure will be the same as the system pressure. The expansion vessel should be measured with zero system pressure reading on the boiler front panel. The water must be going somewhere. Either you have a leak or it is going out past the system overpressure valve. Does the system pressure go up to 3 bar when the central heating is hot? (this will cause loss of water through safety valve). If so recharge expansion vessel.

c
October 2008

Automatic Answer

While you wait for answers, we may have found some information which could help you.

Click here for Boiler Checked Tank Bar

Mend Video, DVD Players
Mend repair fix Vokera dvd players

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Video, DVD Players
Mend repair fix Vokera dvd players