Recent: Fix food processor motor?

Mend Ravenheat Plumbing

Mend D.I.Y, Plumbing
Find out how to mend it for free.

Ask Question
Mend D.I.Y, Plumbing
Find out how to mend Ravenheat plumbing

Mend > Plumbing

Mend Ravenheat System Bar Call Pressure

ravenheat LS80T?

i charge the system to 1.5 bar, when the thermostate call for heat the pressure increases to just under 3 bar. as long as the tempiture stays the same it will hold the pressure in the system. as soon as you turn the temp down , i loss all pressure and have to top up again. Iv changed the preesure relive valve, made no differents.

paul edwards
March 2008
Ckeck the expansion vessel on rear of boiler, should be charged to approx 0.5 to 1 bar pressure (air) use a car tyre foot pump with gauge, you will need to do this with boiler drained and drain plug removed, or you will get false reading from xp vessel. If you get water out of tyre valve on xp vessel then it' s burst and it will require replacing. Also ensure the filling loop is disconnected after use this may cause over pressurizing if passing!

Belly
March 2008

Automatic Answer

While you wait for answers, we may have found some information which could help you.

Click here for System Bar Call Pressure

Mend D.I.Y, Plumbing
Find out how to mend Ravenheat plumbing

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend D.I.Y, Plumbing
Find out how to mend Ravenheat plumbing