Vokera Linea 24, Saftey vale has dischared water. Pressure at 02. bar?
Hello,
I have a Vokera Linea 24 boiler. The heating is not working. The pressure reads 0.2 bar. The saftey valve has discharged water. Manunal say to get an engineer out once this has occured. I have turned the switch to off/reset and the pressure sits at 0.2 - 0.4 bar. Can I resolve this in any way?
refill system using filling loop take up to apr 1.5bar then close filling loop valve, does it hold this pressure? if so reset boiler... does the boiler start watch the pressure is it going up with boiler running if it is then u will need your pressure vessel replenishing or replacing it will rise slightly when running im talking about more than half bar pressure in few mins
sean
November 2009
Automatic Answer
We may have found other answers which could help you.